Modular heat pumps with vapour-injection inverter scroll compressor and R290 natural refrigerant
Conventional heat pumps face a contradiction: as the outdoor temperature falls and the building's demand rises, the heating capacity they deliver tends to drop significantly.
VLP overcomes this limit by combining R290 natural refrigerant with an inverter scroll compressor with enhanced vapour injection (EVI). A secondary subcooling circuit injects refrigerant vapour at intermediate pressure directly into the compressor scrolls. The result is threefold:
- The mass flow rate sent to the condenser increases, stabilising the capacity delivered
- Discharge temperatures are lower, directly extending compressor service life
- The compression ratio remains high without compromising efficiency.
At the design stage, this means significantly less oversizing.
With a GWP (Global Warming Potential) of just 3, among the lowest on the market, VLP complies with the stringent F-Gas Regulation and actively contributes to reducing greenhouse gas emissions.
Plus
- Use of natural refrigerant R290 (GWP = 3)
- Low refrigerant charge (< 10 kg)
- Variable-speed scroll compressor driven by an inverter with vapour injection
- Modularity up to 450 kW
- Very high seasonal efficiency (SCOP up to 4.30)
- Maximum leaving water temperature 75°C
- Leaving water at 67°C with -20°C outdoor air
- Hydraulic configuration for 2-pipe or 4-pipe systems
- Finned coil circuiting designed to ensure counter-flow exchange between air and refrigerant in all operating modes.
Features and Versions
- Complete hydronic kit for 2-pipe or 4-pipe systems
- Electronic expansion valve as standard
- Wide choice of options and accessories
- Advanced logic to secure the unit in the event of refrigerant leaks
- 2 sizes for modular installation in medium- and high-capacity systems
- Reversible heat pump
- Low-noise acoustic versions
Technical characteristics
The two sizes in the Galletti VLP range deliver heating capacities of 50 and 75 kW, scalable up to 450 kW thanks to the modular layout they were designed around. Their inverter control not only matches the capacity delivered to the actual heating load, but also significantly reduces power consumption, both at compressor start-up (lower inrush current) and during part-load operation, achieving seasonal efficiency ratings among the highest in the HVAC market (SCOP up to 4.30).
EVI (Enhanced Vapour Injection) technology optimises the thermodynamic cycle by injecting medium-pressure vapour, stabilising the capacity delivered as the outdoor air temperature falls.
Top-quality components and advanced engineering of the refrigeration, hydraulic and electrical parts are the hallmarks of Galletti VLP units: state-of-the-art heat pumps in terms of efficiency, reliability and operating limits.
Galletti VLP units can produce water from -10°C to 75°C and operate at full load with outdoor air from -20°C to 48°C (the units produce hot water at 67°C even with outdoor air down to -20°C).
The Galletti VLP range also offers extensive acoustic and hydraulic configurability. All the hydraulic components required for 2-pipe or 4-pipe applications can be integrated on board without increasing the footprint: up to 4 pumps (two for the cold circuit and two for the hot circuit), metal strainer, 3-way valves, water safety valves, high-efficiency air separators, non-return valves, shut-off valves, and supply and return headers for installing multiple units in parallel.
The advanced controller, fitted across the entire range, provides continuous monitoring of operating parameters, sophisticated control and connectivity logic, and dedicated safety procedures to secure the unit in the event of refrigerant leaks (A3).
Main components
Do you want more information?
Contact us now by filling out the form